Reverse Power Flow Protection Device

Reverse Power Flow Protection Device

Reverse power flow protection device for 400V distributed energy storage and grid connection systems. Combines electrical measurement, configurable protection, event records and communication, with input ratings and switching logic confirmed for the project.
Nhận báo giá nhanh chóng






    Tổng quan về sản phẩm

    The Henghui reverse power flow protection device combines measurement, protection, control and communication for distributed energy applications. The listed application is at the 400V system level. The device monitors electrical quantities and coordinates switching functions through the approved protection scheme.

    Reverse power flow protection device applications

    Use the project single-line diagram to define the monitoring point and required switching action. First, specify the CT/PT ratios and wiring arrangement. Then confirm the reverse power threshold, time delay and output logic for the installation.

    The system voltage and the device voltage-input rating are different selection items. This product lists a rated input of AC 100V line voltage or 57.7V phase voltage. Confirm the instrument-transformer arrangement before connecting the device to the system.

    Functions and Features

    Electrical measurement and protection

    • Measures voltage, current, frequency, power, power factor and phase angle.
    • Provides reverse power protection and two-stage overvoltage and undervoltage protection.
    • Supports overfrequency, underfrequency and sudden frequency change protection.
    • Includes external intertrip, three-stage overcurrent and zero-sequence overcurrent functions.
    • Provides system power-loss detection and voltage-based closing functions as configured.

    Inputs, outputs and communication

    • 10 external status inputs with configurable names.
    • 4 switching outputs, expandable to 6 according to configuration.
    • Sequence-of-events and fault records, LCD indication and operation logging.
    • RS485 serial interface, with Modbus and IEC 60870-5-101 options as configured.
    • Optional dual Ethernet interfaces; confirm availability for the ordered version.

    Specify the communication protocol and interface quantity when requesting a quotation. The final configuration determines the available connections and functions.

    Technical Specifications

    Application system voltage 400 V system level
    Auxiliary power supply AC/DC 100–264 V
    Rated current input AC 5 A or 1 A; specify when ordering
    Rated voltage input AC 100 V line voltage or 57.7 V phase voltage; confirm instrument-transformer wiring
    Rated frequency 50 Hz
    Operating temperature −10°C to +55°C
    Relative humidity ≤95%, non-condensing
    Atmospheric pressure 86–106 kPa

    Selection and Application Notes

    Confirm the monitoring and switching scheme

    Provide the system single-line diagram, grid connection voltage and CT/PT ratios. Also state the auxiliary supply, required reverse power threshold, time delay and I/O quantity. Include the communication requirements and the equipment that receives the output signals.

    Coordinate the protection settings and switching logic with the project design. Reverse power protection acts through the specified control and switching scheme. Confirm any continuous export-limiting requirement separately when defining the full system scope.

    Check the device inputs before ordering

    Select either the 5A or 1A rated current input to match the CT arrangement. Check the rated voltage input and auxiliary supply against the table above. Final wiring, available functions and communication protocol follow the confirmed device version and project requirements.

    Quotation & Related Products

    Request a reverse power flow protection device quotation

    Send your drawing, required quantity and configuration to Kathy at kathy@nbhh-group.com. Identify any data sheet, connection drawing or inspection record requirements. This helps us prepare a quotation with a clear supply scope.

    Khám phá anti-islanding protection relay và photovoltaic grid connection cabinet for related grid connection equipment. Each product performs a different role in the overall project.

    Bạn đang lên kế hoạch cho một dự án phân phối điện hoặc năng lượng tái tạo?

    Nhận hỗ trợ kỹ thuật và báo giá tùy chỉnh

    • Hơn 15 năm kinh nghiệm trong ngành
    • Dòng sản phẩm đầy đủ về kết nối lưới điện và bù đắp
    • Phục vụ khách hàng tại hơn 30 quốc gia
    • Hơn 100 quyền sở hữu trí tuệ
    • 12% Doanh thu hàng năm được tái đầu tư vào nghiên cứu và phát triển (R&D) và đổi mới.
    • Hỗ trợ kỹ thuật toàn diện và thiết kế kỹ thuật tùy chỉnh

    Yêu cầu báo giá