Relais zum Schutz vor Inselbetrieb

Relais zum Schutz vor Inselbetrieb

Anti-islanding protection relay for distribution transformer and renewable energy grid connection applications. Provides configurable protection, event records, switch-status monitoring and RS485 communication for integration into the project protection scheme.
Schnelles Angebot einholen






    Produktübersicht

    The Henghui anti-islanding protection relay monitors electrical conditions at grid connection points. It provides control signals to help isolate distributed generation when it detects abnormal grid conditions. Panel builders can integrate the device into a control panel or switchgear cabinet as part of the project protection scheme.

    Anti-islanding protection relay applications

    Typical applications include the low-voltage side of distribution transformers and renewable energy grid connections. First, define the connection diagram and required protection functions. Then match the relay inputs, auxiliary supply and output contacts to the approved design.

    The relay provides protection signals to the switching circuit. The complete protection scheme also requires suitable switching equipment, wiring and coordinated settings. Confirm those details for the selected configuration before installation.

    Funktionen und Merkmale

    Protection and switching functions

    • Two-stage overvoltage, undervoltage, overfrequency, underfrequency and reverse power protection.
    • Sudden frequency change protection, overcurrent and overload protection.
    • Instantaneous and time-delayed trip functions, plus voltage-recovery closing as configured.
    • Anti-pumping circuit and switch-status monitoring.

    Inputs, records and communication

    • 10 passive switch-status inputs and 3 dry-contact relay outputs.
    • 4 AC current inputs and 4 AC voltage inputs.
    • 6-channel non-electrical protection inputs.
    • CT/PT circuit-disconnection alarms, event records and fault waveform recording.
    • Standard RS485 communication for connection to the specified monitoring system.

    Confirm the communication protocol, contact ratings and available functions for the ordered version. Panel mounting and individual switchgear installation depend on the project layout.

    Technische Daten

    Auxiliary power supply AC 85–450 V or DC 100–370 V
    Rated AC current input 5 A or 1 A
    Rated AC voltage 380 V
    Nennfrequenz 50 Hz
    Betriebstemperatur −10°C to +55°C
    Storage temperature −40°C to +85°C
    Relative humidity ≤95%, non-condensing
    Atmospheric pressure 80–110 kPa
    Current-circuit burden ≤0.5 VA per phase at 5 A
    Voltage-circuit burden ≤0.8 VA per phase at 380 V
    Device power consumption ≤5 W as listed in the catalogue
    Kommunikation RS485

    Hinweise zur Auswahl und Anwendung

    Define the relay wiring and settings

    Provide the grid connection diagram, transformer data and CT ratios. Also specify the voltage-input arrangement, auxiliary supply and required trip or closing logic. These details help confirm the relay configuration and the interface to the switching equipment.

    Coordinate anti-islanding and reclosing settings with the project grid connection requirements. Confirm the operating thresholds and time delays during the design review. Qualified personnel should complete wiring checks and functional tests before commissioning.

    Confirm the selected version

    The table above retains the specifications listed for this product. Final wiring, dimensions, communication protocol and available functions follow the confirmed device version. Request the relevant data sheet and connection drawing with your quotation.

    Quotation & Related Products

    Request an anti-islanding protection relay quotation

    Email Kathy at kathy@nbhh-group.com with the quantity, application and required functions. Attach the single-line diagram and state any documentation or test requirements. We can then review the configuration and quotation scope.

    For related equipment, see our photovoltaic grid connection cabinet und reverse power flow protection device. Select each device according to its role in the approved protection scheme.

    Planen Sie ein Projekt im Bereich Stromverteilung oder erneuerbare Energien?

    Technischen Support und ein individuelles Angebot anfordern

    • Über 15 Jahre Branchenerfahrung
    • Komplette Palette von Netzanschluss- und Kompensationsprodukten
    • Wir betreuen Kunden in über 30 Ländern
    • Über 100 Rechte an geistigem Eigentum
    • 12% Jährliche Einnahmen, die in FuE und Innovation reinvestiert werden
    • Technischer Support und kundenspezifische Entwicklung über den gesamten Zyklus

    Angebot einholen

      de_DEDeutsch